Scroll or digital scroll compressor models, Table 12 – Liebert Precision Cooling System DS User Manual

Page 30

Advertising
background image

Liebert DS Dimensions and Weights

20

Figure 15 Cabinet and floor planning dimensions—upflow, air-cooled 28-42kW (8-12 ton), scroll or digital

scroll compressor models

Table 12

Weight for upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressor models

Model No.

Dry Weight, lb (kg)

approximate

028-042

Air-Cooled

1520 (689)

Dual-Cool

1670 (758)

Alternate Refrigerant
Piping Entrance

3/4"

(19mm)

Bezels

24"

(610mm)

34"

(864mm)

72"

(1829mm)

FRONT VIEW

DPN001163

Rev. 1

Shaded area indicates a
recommended minimum
clearance for component
access.

2"

(51mm)

76"

(1930mm)

1-1/2"

(38mm)

TOP VIEW

73"

(1854mm)

High Volt Connection(s)

35"

(889mm)

33"

(838mm)

Minimum required

for blower replacement

Low Volt Connection(s)

Note: Front air return unit shown. For rear

return unit, in addition to front service area

shown, also include 25" (635mm) on one side

of unit for access to rear return filter box.

See DPN001196, Figure 28.