Liebert DS Dimensions and Weights

29

Figure 24 Floor stand dimensions—downflow, 105kW (30 ton) models

Table 21

Floor stand and floor planning dimensions—downflow, 105kW (30 ton) models

Height, in. (mm)

C*

D turning vane

9 (229)

4 (111)

12 (305)

7 (187)

15 (381)

10 (264)

18 (457)

13 (340)

21 (533)

16 (416)

24 (610)

19 (492)

D

DPN001059
REV 1

NOTE: Right side of paneled unit is flush with right side of floorstand. All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.

Gussets supplied
on floor stands 12" (305 mm)
tall and greater

Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.

Supply air

discharge

opening

Optional turning vane
shown as front air discharge.

Supply air
discharge opening

33"

(838mm)

34-1/2"

(876mm)

(with feet)

132-1/2"

(3366mm) (with feet)

26"

(660mm)

91-3/4"

(2330mm)

131"

(3327mm)

16-3/4"

(425mm)

1"

(25mm) TYP.

3"

(76mm)

7/8"

(23mm)

4-1/2"

(114mm)