The Liebert DS product is a single component in the facility heat removal system. The system

includes air distribution (raised floors, duct systems), outdoor heat rejection (condensers, pumps, dry-

coolers, cooling towers, piping, heat rejection fluid, ambient temperature, etc.) and indoor cooling and

humidity loads (equipment load, location, outside air infiltration). Proper application and mainte-

nance of the entire system is critical to the life and reliability of the Liebert DS.

• Good maintenance practices are essential to minimizing operation costs and maximizing product

life.

• Read and follow monthly and semi-annual maintenance schedules included in this manual. These

MINIMUM maintenance intervals may need to be more frequent based on site-specific conditions.

• See the iCom user manual, SL-18835, for instructions on how to utilize the unit controller to pre-

dict some service maintenance intervals.

• Emerson recommends the use of trained and authorized service personnel, extended service con-

tracts and factory-specified replacement parts. Contact your local Emerson representative.

12.1 Filters

To maximize the performance and reliability of Liebert DS equipment, use only Liebert filters. Con-

tact your local Emerson representative to order replacement filters.

!

WARNING

Risk of electric shock. Can cause injury or death.
Disconnect local and remote power supplies before working within.
Before proceeding with installation, read all instructions, verify that all the parts are included

and check the nameplate to be sure the voltage matches available utility power.
Follow all local codes.

!

WARNING

Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,

injury or death.
Only qualified service personnel should work on this equipment.
Read all installation, operating and safety instructions before proceeding.
Read and follow all warnings in this manual

!

CAUTION

Risk of improper filter installation and filter collapse. Can cause equipment damage.
Pleat direction is non-standard. Use only short-pleat filters (see Figure 82). Long-pleat filters

are subject to collapse at high airflows.

Table 53

Filter quantities, downflow units

Unit Size

Filter Size

Width x Length

Filter Quantities

4" Filter Option

Merv 8 or Merv 11

2" Primary / 2" Pre-Filter Option

Merv 11 Primary Filter / Merv 7 Pre-Filter

DS 028, 035, 042

16 x 25

5

5/5

DS 053, 070, 077

7

7/7

DS 105

9

9/9

Table 54

Filter quantities, upflow units

Upflow Models

Filter Size

Width x Length

Filter Quantities

4" Filter Option Merv 8 or Merv 11

2" Primary/2" Pre-Filter Option

Merv 11 Primary/Merv 7 Pre-Filter

VS025, 035, 042

25 x 20"

4

4/4

VS053, 070, 077

6

6/6

VS105