77kw (15-22 ton), all compressor models, Table 16 – Liebert Precision Cooling System DS User Manual

Page 34

Advertising
background image

Liebert DS Dimensions and Weights

24

Figure 19 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton),

all compressor models

Table 16

Weights for upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models

Compressor Type

Dry Weight, lb (kg) approximate

Model

053

070, 077

Semi-Hermetic Compressor

Water/Glycol

2650 (1205)

2800 (1270)

GLYCOOL/Dual-Cool 2830

(1287)

2980

(1352)

Scroll or Digital Scroll Compressor

Water/Glycol

2370 (1075)

GLYCOOL/Dual-Cool

2550 (1157)

DPN001167
Rev. 1

Top View

Front View

High Volt Connection(s)

Alternate Condenser
Fluid Piping Entrance

Low Volt
Connection(s)

Shaded area indicates a
recommended minimum
clearance for component
access.

3/4"

(19mm)

Bezels

35"

(889mm)

33"

(838mm)

76"

(1930mm)

2"

(51mm)

109"

(2769mm)

108"

(2743mm)

1-1/2"

(38mm)

24"

(610mm)

34"

(864mm)

Minimum required

for blower replacement

Required for

condenser cleanout

Note: Front air return unit shown. For rear return unit,

in addition to front service area shown, also include

25" (635mm) on one side of unit for access to rear return

filter box. See DPN001196, Figure 28.