Semi-hermetic compressor models, Table 14 – Liebert Precision Cooling System DS User Manual

Page 32

Advertising
background image

Liebert DS Dimensions and Weights

22

Figure 17 Cabinet and floor planning dimensions—upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic

compressor models

Table 14

Weights for upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models

Model

Dry Weight, lb (kg)

approximate

053

070, 077

Air

-Cool

ed

2350 (1069)

2500 (1134)

Dual

-Cool

2530 (1150)

2680 (1216)

DPN001165
Rev. 1

Top View

Front View

High Volt Connection(s)

Alternate Refrigerant
Piping Entrance

Low Volt Connection(s)

Shaded area indicates a
recommended minimum
clearance for component
access.

3/4"

(19mm)

Bezels

35"

(889mm)

33"

(838mm)

76"

(1930mm)

2"

(51mm)

109"

(2769mm)

108"

(2743mm)

1-1/2"

(38mm)

24"

(610mm)

34"

(864mm)

Minimum required

for blower replacement

Note: Front air return unit shown. For rear return unit,

in addition to front service area shown, also include

25" (635mm) on one side of unit for access to rear return

filter box. See DPN001196, Figure 28.