Liebert DS Dimensions and Weights

21

Figure 16 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all

compressor models

Table 13

Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models

Compressor Type

Dry Weight, lb (kg) approximate

Model

028-042

Semi-Hermetic

Water/Glycol

1980 (898)

GLYCOOL/Dual-Cool 2130

(966)

Scroll or Digital Scroll

Water/Glycol 1830

(830)

GLYCOOL/Dual-Cool

1980 (898)

DPN001164
Rev. 1

Alternate Refrigerant
Piping Entrance

3/4"

(19mm) Bezels

24"

(610mm)

34"

(864mm)

85"

(2159mm)

FRONT VIEW

Shaded area indicates a
recommended minimum
clearance for component
access.

2"

(51mm)

76"

(1930mm)

1-1/2"

(38mm)

TOP VIEW

86"

(2184mm)

High Volt Connection(s)

Condenser Cleanout Access

35"

(889mm)

33"

(838mm)

Minimum required

for blower replacement

Required for

condenser cleanout

Low Volt Connection(s)

Note: Front air return unit shown. For rear

return unit, in addition to front service area

shown, also include 25" (635mm) on one side

of unit for access to rear return filter box.

See DPN001196, Figure 28