1 removing the unit from the skid with a forklift, Figure 32 remove the unit from the skid, Removing the unit from the skid with a forklift – Liebert Precision Cooling System DS User Manual

Page 47: Warning

Advertising
background image

Equipment Inspection and Handling

37

5.2.1 Removing the Unit from the Skid With a Forklift

1. Align a forklift with either the front or rear side of the unit.

2. Insert the tines of the forklift completely under the base of the Liebert DS.

3. Remove the lag bolts from each bracket holding the Liebert DS to the skid.
4. Lift the unit off the skid—no more than 6" (152mm)—and remove the skid.

Figure 32 Remove the unit from the skid

!

WARNING

Risk of improper moving. Can cause equipment damage, injury or death.
Use the center of gravity indicators on the unit to determine the entry points for the tines (see

Figure 34). The center of gravity varies depending on the unit size and selected options.
The forklift’s tines must be equally spaced on either side of the center of gravity indicator.

!

WARNING

Risk of improper moving. Can cause equipment damage, injury or death.
Ensure that the tines are level, not angled up or down.
The tines must be at a height that will allow proper clearance under the unit.
Ensure the tines extend beyond the opposite side of the unit.

Step 1

Step 2

Step 3

Step 4

181659P1

Rev. 5

Advertising