Table 47, Table 48 – Liebert Precision Cooling System DS User Manual

Page 87

Advertising
background image

Piping

77

Table 47

Line charges - refrigerant per 100 ft (30m) of Type “L” copper tube

O.D.

Liquid Line, lb (kg)

1/2" 7.3

(3.3)

5/8" 11.7

(5.3)

7/8" 24.4

(11.1)

1-1/8"

41.6 (18.9)

Table 48

Outdoor condenser approximate refrigerant charge lb (kg) per circuit

Model

Fan

Speed

Lee-Temp

(includes receiver)

165

5 (2.3)

27 (12.3)

205

7 (3.2)

38 (17.2)

251

10 (4.6)

38 (17.20

308

11 (5.0)

58 (26.3)

415

15 (6.8)

75 (34.0)

510

30 (13.6)

149 (67.6)

143

17 (8)

64 (29)

214

23 (10

81 (37)

286

29 (13)

98 (44)

409

36 (16)

129 (59)

477

24 (11)

80 (36)

572

57 (26)

196 (89)

Advertising