Table 20 – Liebert Precision Cooling System DS User Manual

Page 38

Advertising
background image

Liebert DS Dimensions and Weights

28

Figure 23 Floor stand dimensions—downflow, 53-77kW (15-22 ton) models

Table 20

Floor stand and floor planning dimensions—downflow, 53-77kW (15-22 ton) models

Dimensions, in. (mm)

Height, in. (mm)

Model

A

B

C*

D Turning Vane

Air-Cooled Semi-Hermetic Models and

All Water/Glycol/GLYCOOL Models

108

(2743)

26

(660)

9 (229)

4 (111)

12 (305)

7 (187)

15 (381)

10 (264)

Air-Cooled Scroll Models and

Air-Cooled Digital Scroll Models

97

(2464)

15

(381)

18 (457)

13 (340)

21 (533)

16 (416)

24 (610)

19 (492)

DPN000930
REV 1

NOTE: Right side of paneled unit is flush with right side of floor stand. All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height C.

Gussets supplied
on floor stands 12" (305 mm)
tall and greater

Turning vane air outlet
Optional turning vane can be field-installed
in supply air discharge opening for front or
rear air discharge.

Supply air

discharge

opening

Optional turning vane
shown as front air discharge.

Supply air
discharge opening

34-1/2"

(876mm)

(with feet)

A+1-1/2"

(38mm) (with feet)

33"

(838mm)

69-3/4"

(1772mm)

16-3/4"

(425mm)

1"

(25mm) TYP.

3"

(76mm)

7/8"

(23mm)

4-1/2"

(114mm)

A

B