Liebert Precision Cooling System DS User Manual

Page 108

Advertising
background image

Piping Schematics

98

Figure 73 Primary connection locations—downflow, air-cooled, 105kW (30 ton), all compressor models

Point

Description)

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

W

Water/Glycol/GLYCOOL Access

125-15/16 (3199)

9 (229)

3-1/2 x 8 (89 x 203)

WS

Water/Glycol/GLYCOOL Supply

127-7/8 (3248)

10-1/16 (256)

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

127-7/8 (3248)

13-1/4 (337)

2-1/8 Cu Sweat

CD

Condensate Drain *

83-13/16 (2129)

30 (762)

3/4 FPT

W/ Optional Pump

83-13/16 (2129)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

102-3/4 (2610)

31-3/4 (806)

1/4 Cu Sweat

ECS

Econ-O-Coil Supply

101-7/8 (2588)

29 (737)

2-5/8 Cu Sweat

ECR

Econ-O-Coil Return

94-9/16 (2402)

29 (737)

2-5/8 Cu Sweat

HS

Hot Water Reheat Supply

Consult Factory

HR

Hot Water Reheat Return

Consult Factory

E1

Electrical Connection (High Volt)

98-1/4 (2496)

30 (762)

2-1/2

E2

Electrical Connection (High Volt)

88-7/16 (2246)

30 (762)

2-1/2

LV1

Electrical Connection (Low Volt)

2 (51)

27-1/2 (796)

7/8

LV2

Electrical Connection (Low Volt)

2 (51)

30-1/4 (768)

7/8

LV3

Electrical Connection (Low Volt)

2 (51)

32 (813)

7/8

B1

Blower Outlet

28-1/4 (718)

18 (457)

14-1/2 x 15-7/8 (368 x 403)

B2

Blower Outlet

52 (1321)

18 (457)

14-1/2 x 15-7/8 (368 x 403)

B3

Blower Outlet

75-11/16 (1922)

18 (457)

14-1/2 x 15-7/8 (368 x 403)

* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on Dual-Cool systems only (4-pipe system)

35"

(889mm)

All dimensions
from rear corner
of unit including
panels

3-1/2"

(89mm)

Section A-A

Front View

A

A

X

Y

O

Tolerance on all
piping dimensions
is ± 1/2" (13mm)

131"

(3327mm)

Front of Unit

Note: Drawing not to scale

DPN001015
Rev. 2

WS

W

LV3

LV2

LV1

ECS

HUM

CD

ECR

E1 E2

B1

Blower

Outlet

Blower

Outlet

Blower

Outlet

B2

B3

8" (203mm)

15-7/8"

(403mm)

WR

14-1/2"

(368mm)

Typ