0 piping schematics, Iping, Chematics – Liebert Precision Cooling System DS User Manual

Page 92: Figures 57

Advertising
background image

Piping Schematics

82

9.0

P

IPING

S

CHEMATICS

Figure 57 Piping schematic—air-cooled, semi-hermetic compressor models

Condenser Coil

(Lee-Temp)

Condenser Coil

(Fan Speed )

Check Valve

Relief Valve

Service

Valve

Liquid Return

Head Pressure

Control Valve

Lee-Temp Receiver

Hot Gas Discharge

Evaporator Coil

Lee-Temp

Compressor

Muffler

Service
Valve

External
Equalizer

Liquid

Sensing
Bulb

Inverted trap on discharge and liquid
lines to extend above base of coil by
a minimum of 7-1/2” (190mm).

Field-installed relief valve (s)
required for 50Hz EU CE units rated
maximum 480 PSIG (33 Bar).

* Isolation

valve

* Isolation

valve

** Muffler

* Traps every

25ft (7.6m)
of rise

Fusible
Plug

Suction

Hot Gas Discharge

Liquid Return

Filter Dryer

Sight Glass

Solenoid
Valve

Expansion
Valve

Refrigerant Piping
Field Piping

Service/Schrader (Access) Connection No Valve Core

Note: Schematic representation shown . Do not use for specific connection locations .

Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .

Service
Valve

Cylinder
Unloader (s)

DPN000797
Rev. 3

Service/Schrader (Access) Connection With Valve Core

Components are not supplied by
Liebert, but are recommended for
proper circuit operation and
maintenance.
Components supplied by Liebert and
must be field-installed (70kW, 77kW
and 105kW models only).

*

**