Fan speed charging, Table 49, Fan speed suction pressure transducer settings – Liebert Precision Cooling System DS User Manual

Page 89: To fan speed, Charging, Caution

Advertising
background image

Piping

79

Fan Speed Charging

1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending

on refrigerant type.

2. Refrigerant charging requires unit operation. Refer to 10.0 - Checklist for Completed

Installation.

3. Calculate the amount of charge for the system. Refer to the unit, condenser and refrigerant line

charge data in Tables 46, 47 and 48.

4. Weigh in as much of the system charge as possible before starting the unit.

5. Turn on unit disconnect switch. Operate the unit for 30 minutes using the charging function for

System #1 and System #2 in the diagnostic section of the iCOM control (see iCOM user manual,

SL-18835). The charging function operates the compressor at full capacity and energizes the

blower motor and the liquid line solenoid valve. The reheat and humidifier are disabled. A

minimum 20psig (138kPa) must be established and maintained for the compressor to operate.

The charging function can be reset as many times as required to complete unit charging.

6. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound

(2.2kg) of refrigerant.

7. As head pressure builds, the fan speed controlled condenser fan begins rotating. The fan will run at

full speed when sufficient head pressure is developed—fan starts to rotate at 190 psig (1310 kPA)

and is full speed at 250 psig (1724 kPA).

!

CAUTION

Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant R407C is a blend of three components and must be introduced and charged from

the cylinder only as a liquid.
When adding liquid refrigerant to an operating system, it may be necessary to add the

refrigerant through the compressor suction service valve. Care must be exercised to avoid

damage to the compressor. Emerson recommends connecting a sight glass between the

charging hose and the compressor suction service valve. This will permit adjustment of the

cylinder hand valve so that liquid can leave the cylinder while allowing vapor to enter the

compressor.

Table 49

Fan speed suction pressure transducer settings

Function

R-22

R-407C

Gauge (Sea Level)

Absolute

Gauge (Sea Level)

Absolute

psiG (kPa)

psiA (kPa)

psiG (kPa)

psiA (kPa)

Pump-Down Cutout

20 (138)

35 (241)

20 (138)

35 (241)

Pump-Down Reset

65 (448)

80 (552)

65 (448)

80 (552)

Minimum to Start-Cooling

35 (241)

50 (344)

35 (241)

50 (344)

Low-Pressure Cutout (DX only)

48 (331)

63 (434)

52 (358)

67 (461)

NOTE
A digital scroll compressor will have a clear sight glass only when operating at 100% capacity.

When operating below 100%, the sight glass may show bubbles with each 15-second unloading

cycle.