Piping Schematics

83

Figure 58 Piping schematic—air-cooled, scroll compressor models

Lee-Temp Receiver

Fan Speed

Lee-Temp

Service
Valve

External
Equalizer

Liquid

Sensing
Bulb

Inverted trap on discharge & liquid
lines to extend above base of coil
by a minimum of 7-1/2” (190mm).

Field installed relief valve (s) required
for 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar).

* Isolation
valve

* Traps every
25ft (7.6m)
of rise

Fusible
Plug

Suction

Hot Gas Discharge

Liquid Return

Filter Dryer

Sight Glass

Solenoid
Valve

Expansion
Valve

DPN000798
Rev. 2

Condenser Coil

(Fan Speed )

Condenser Coil

(Lee-Temp)

Evaporator Coil

Compressor

Service
Valve

Check
Valve

* Isolation
valve

(Required with Digital Scroll)

28-42kW Digital Solenoid Valve

53-70kW Digital

Solenoid Valve

Refrigerant Piping
Field Piping

Service/Schrader (Access) Connection No Valve Core

Note: Schematic representation shown . Do not use for specific connection locations .

Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .

Service/Schrader (Access) Connection With Valve Core

Liquid Return

Hot Gas

Discharge

Head Pressure

Control Valve

Check
Valve

Relief
Valve

Service
Valve

Components are not supplied by
Liebert, but are recommended
for proper circuit operation and
maintenance.

*