Customer heat rejection – Liebert Precision Cooling System DS User Manual

Page 95

Advertising
background image

Piping Schematics

85

Figure 60 Piping schematic—water/glycol with scroll compressor models

COMPRESSOR

CUSTOMER

HEAT REJECTION

COOLING TOWER

AND PUMP

SYSTEM

BY OTHERS

RETURN SUPPLY

LIEBERT

HEAT REJECTION

DRYCOOLER

(Glycol)

Aquastat
Sensing
Bulbs

EXPANSION

TANK**

Hose
Bib*

Shutoff Valve*

Pressure
Port*

Optional Dual Pump System shown

RETURN

RETURN

SUPPLY

SUPPLY

Air Vents
(typical)***

Hose
Bib*

Hose
Bib*

Optional
3-Way Regulating
Valve

2-Way
Regulating
Valve

Bypass Valve

PARADENSER

CONDENSER

Hot Gas Reheat
Valve

Check Valve

EVAPORATOR

COIL

HOT GAS REHEAT

Sensing Bulb

Service
Valve

External
Equalizer

Service
Valve

Check
Valve

DISCHARGE

LIEBERT DS

(and associated piping)

LIQUID

SUCTION

Expansion
Valve

Solenoid
Valve

Sight
Glass

Filter Dryer

Relief valve(s) supplied
with 50Hz EU CE units rated
maximum 480 PSIG (33 Bar)

TO SECOND

REFRIGERATION

CIRCUIT

Sensor

Optional Factory Piping

* Components are not supplied by
Liebert but are recommended for
proper circuit operation and
maintenance
** Field-installed at highest point in
system on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points

DPN000896
REV 3

Check Valves*
(on Dual Pump
Systems only)
Gate Valves*

Pressure Port*

Flow Switch
Supplied with Dual
Pump Systems

Flow-Regulating
Valve*

GLYCOL

PUMPS

Shutoff Valve*

Shutoff Valve*

Shutoff Valve*

Factory Piping
Field Piping

Service/Schrader (Access) Connection No Valve Core

Service/Schrader (Access) Connections With Valve Core

Note: Schematic representation shown. This schematic does not imply or define elevations and
component location unless specifically noted.

Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.

®

For systems with drycoolers,

refer to 12.11.3 - Drycooler Settings.