Compressor models – Liebert Precision Cooling System DS User Manual

Page 112

Advertising
background image

Piping Schematics

102

Figure 77 Primary connection locations—upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic

compressor models

Point

Description

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

R1

Refrigerant Access (Top)

83-3/4 (2127)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

R2

Refrigerant Access (Bottom)

86 (2184)

13-7/8 (352)

16-7/16 x 4 (418 x 102)

53kW (15 ton)/70 & 77kW (20 & 22 ton)

L1

Liquid Line System 1

97 (2464)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

93-5/16 (2370)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

90-5/8 (2302)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

88 (2235)

16-5/8 (422)

7/8 / 1-1/8 Cu Sweat

R3

Refrigerant Access (Side)

-

-

6 x 17-3/16 (152 x 437)

CGD* Condensate Gravity Drain

-

-

3/4 FPT

CPD

Condensate Pump Discharge (Opt)

79-5/16 (2015)

11-7/8 (302)

1/2 Cu Sweat

HUM

Humidifier Supply Line

79-5-16 (2015)

9-7/8 (251)

1/4 Cu Sweat

ECS** Econ-O-Coil Supply

78-5/8 (1998)

7-7/8 (200)

2-1/8 Cu Sweat

ECR** Econ-O-Coil Return

78-5/8 (1998)

4-5/8 (117)

2-1/8 Cu Sweat

E1

Electrical Connection (High Voltage)

75-3/8 (1915)

30 (762)

2-1/2

E2

Electrical Connection (High Voltage)

69-7/8 (1775)

30 (762)

2-1/2

LV1

Electrical Connection (Low Voltage)

19-1/2 (495)

29-1/16 (738)

7/8

LV2

Electrical Connection (Low Voltage)

19-1/2 (495)

30-1/2 (775)

7/8

LV3

Electrical Connection (Low Voltage)

19-1/2 (495)

31-15/16 (811)

7/8

* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
** Supplied on Dual-Cool systems only (4-pipe system)

NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
3. Field routed alternatives for refrigerant
gas and liquid line connection points.
4. See submittal page DPN001191 for
blower outlet and deck dimensional data.

6"

(152mm)

20-1/16"

(509mm)

Factory Location

DPN001212
Rev. 2

LEFT SIDE SECTION VIEW OF UNIT

FRONT SECTION VIEW OF UNIT

(Left Front Panel Not Shown)

14-1/4"

(362mm)

15-7/8"

(403mm)

3-7/8"

(98mm)

17-3/16"

(437mm)

TOP VIEW OF UNIT

All dimensions from
rear corner of unit
including panels

X

O

Y

16-7/16"

(418mm)

15-3/16"

(386mm)

22-1/2"

(572mm)

35"

(889mm)

109" (2769mm)

Blower

Outlet

Blower

Outlet

4"

(102mm)

Front of Unit

* Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
** Supplied on Dual Cooling Systems only

3

3

3