All compressor models, Table 10 – Liebert Precision Cooling System DS User Manual

Page 28

Advertising
background image

Liebert DS Dimensions and Weights

18

Figure 13 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 105kW (30 ton), all

compressor models

Table 10

Weights for downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models

Compressor Type

Dry Weight, lb (kg) approximate

Model

105

Semi-Hermetic Compressor

Water/Glycol

3410 (1550)

GLYCOOL/Dual-Cool

3770 (1714)

Scroll Compressor

Water/Glycol

3290 (1495)

GLYCOOL/Dual-Cool

3650 (1659)

35"

(889mm)

132"

(3353mm)

76"

(1930mm)

131"

(3327mm)

34"

(864mm)

Shaded area indicates a
recommended minimum
clearance for component
access.

15"

(381mm)

3/4"

(19mm)

24-3/8"

(619mm)

102-13/16"

(2611mm)

Secondary Condenser
Fluid Entrance

Air Inlet Opening

Opening

Opening

Bezels

Secondary Entrance
Low Volt Connections

Minimum required

for filter replacement

Secondary Entrance
High Volt Connection(s)

Top View

Front View

Notes: Filters are accessible

only through top of unit.

Downflow

electrical

connections can be made

from top or bottom of unit.

Condenser Cleanout Access

33"

(838mm)

24"

(610mm)

Required for

condenser cleanout

DPN001013

Rev. 2

Advertising