Compressor models – Liebert Precision Cooling System DS User Manual

Page 105

Advertising
background image

Piping Schematics

95

Figure 70 Primary connection locations—downflow, air-Cooled, 53-77kW (15-22 ton) with scroll

compressor models

Point

Description

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

R

Refrigerant Access

81-3/4 (2076)

14-3/4 (374)

12-3/16 x 4 (310 x 102)

53kW (15ton) / 70 & 77kW (20 & 22ton)

L1

Liquid Line System 1

94-11/16 (2405)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

L2

Liquid Line System 2

91-7/8 (2334)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

G1

Hot Gas Discharge 1

88-3/4 (2254)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

85-9/16 (2173)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

CD

Condensate Drain *

69-1/4 (1759)

30 (762)

3/4 FPT

W/ Optional Pump

69-1/4 (1759)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

ECS**

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

ECR**

Econ-O-Coil Return

72 (1829)

29 (737)

2-1/8 Cu Sweat

HS

Hot Water Reheat Supply

Consult Factory

HR

Hot Water Reheat Return

Consult Factory

E1

Electrical Connection (High Volt)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Connection (High Volt)

75-3/8 (1915)

31-1/8 (790)

2-1/2

LV1

Electrical Connection (Low Volt)

1-7/8 (48)

28-1/2 (724)

7/8

LV2

Electrical Connection (Low Volt)

1-7/8 (48)

30-1/4 (768)

7/8

LV3

Electrical Connection (Low Volt)

1-7/8 (48)

32 (813)

7/8

B1

Blower Outlet (15 x 15)

23-1/8 (587)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

Blower Outlet (15 x 11)

27-3/4 (705)

18-1/16 (459)

14-3/4 x 16-1/16 (375 x 408)

B2

Blower Outlet (15 x 15)

50-3/8 (1280)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

Blower Outlet (15 x 11)

54-3/8 (1381)

18-1/16 (459)

14-3/4 (375) x 16-1/16 (408)

* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do

not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.

** Supplied on Dual Cool systems only (4 pipe system)

Section A-A

Front View

16-1/16"

(408mm)

A

A

X

Y

O

Tolerance on all
piping dimensions
is ± 1/2" (13mm)

Note: Drawing not to scale

DPN000929
Rev. 2

4" (102mm)

LV3

LV2

LV1

ECS

HUM

CD

ECR

E1 E2

B2

12-3/16"

(310mm)

L1 L2

G 1 G2

Blower

Outlet

B1

Blower

Outlet

R

98"

(2489mm)

Front of Unit

35"

(889mm)

All dimensions
from rear corner
of unit including
panels