8. After four hours, check the pressure readings and, if they have not changed, break vacuum with

dry nitrogen. Pull a second (R-407C and R-22) and third (R407C only) vacuum to 250 microns or

less. Recheck the pressure after two hours. After completing this step, proceed to Fan Speed

Charging on page 79.

9. Remove the jumper hose installed previously from between the service valve fitting and the

condenser. After completing this step, proceed to Lee-Temp Charging.

Lee-Temp Charging

1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending

on refrigerant type.

2. Refrigerant charging requires unit operation. Refer to 10.0 - Checklist for Completed

Installation.

3. Calculate the amount of charge for the system. Refer to the unit, condenser and refrigerant line

charge data in Tables 46 and 47.

4. Weigh in as much of the system charge as possible before starting the unit.

5. Turn on unit disconnect switch. Operate the unit for 30 minutes using the charging function for

System # 1 and System # 2 in the diagnostic section of the iCOM control. The charging function

operates the compressor at full capacity and energizes the blower motor and liquid line solenoid

valve. The reheat and humidifier are disabled. A minimum 20psig (138kPa) must established and

maintained for the compressor to operate. The charging function can be reset as many times as

required to complete unit charging.

6. Charge the unit until the liquid line sight glass becomes clear. Then add one additional pound

(2.2 kg) of refrigerant.

Lee-Temp Receiver Refrigerant Level

On each receiver at the condenser are two refrigerant-level sight glasses. Refrigerant level will vary

with outside temperature. Check refrigerant level after the unit has been on for at least 15 minutes.
Sight Glass Levels

40°F (4.5°C) and lower—bottom sight glass is 3/4 full
40 to 60°F (4.5 to 15.5°C)—bottom sight glass is full
60°F (15.5°C) and higher—top sight glass is 3/4 full.

!

CAUTION

Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant R407C is a blend of three components and must be introduced and charged from

the cylinder only as a liquid.
When adding liquid refrigerant to an operating system, it may be necessary to add the

refrigerant through the compressor suction service valve. Care must be exercised to avoid

damage to the compressor. Emerson recommends connecting a sight glass between the

charging hose and the compressor suction service valve. This will permit adjustment of the

cylinder hand valve so that liquid can leave the cylinder while allowing vapor to enter the

compressor.

Table 50

Lee-Temp suction pressure transducer settings

Function

R-22

R-407C

Gauge Reading

(Sea Level)

Absolute

Gauge Reading

(Sea Level)

Absolute

psiG (kPa)

psiA (kPa)

psiG (kPa)

psiA (kPa)

Pump-Down Cutout

20 (138)

35 (241)

20 (138)

35 (241)

Pump-Down Reset

65 (448)

80 (552)

65 (448)

80 (552)

Minimum to Start-Cooling

50 (345)

65 (448)

50 (345)

65 (448)

Low-Pressure Cutout (DX only)

48 (331)

63 (434)

52 (358)

67 (461)

NOTE
A digital scroll compressor will have a clear sight glass only when operating at 100% capacity.

When operating below 100%, the sight glass may show bubbles with each 15-second unloading

cycle.