Condensate pump, Downflow ds unit upflow ds unit, Correct incorrect correct – Liebert Precision Cooling System DS User Manual

Page 83: Incorrect

Advertising
background image

Piping

73

Figure 56 Gravity drain for downflow and upflow units

Condensate Pump

• 1/2" copper sweat connection is provided on units with optional factory-installed condensate

pump

• Condensate Pump (60Hz): Condensate pump is rated for approximately 400 gph at 10 feet total

head

• Condensate Pump (50Hz): Condensate pump is rated for approximately 315 gph at 10 feet total

head

• Size piping based on available condensate head

CORRECT

INCORRECT

CORRECT

DOWNFLOW DS UNIT

UPFLOW DS UNIT

UNIT

INTERNAL
DRAIN

EXTERNAL
DRAIN

CONTINUOUS DOWNWARD SLOPE

INTERNAL
DRAIN

UNIT

UNIT

EXTERNAL
DRAIN

INCORRECT

INTERNAL
DRAIN

EXTERNAL
DRAIN

THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH
UNINTENTIONAL. LINES MUST BE RIGID ENOUGH
NOT TO BOW OVER TOP OF OTHER OBJECTS.

INCORRECT

INCORRECT

THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH
UNINTENTIONAL. LINES MUST BE RIGID ENOUGH
NOT TO BOW OVER TOP OF OTHER OBJECTS.

INTERNAL
DRAIN

EXTERNAL
DRAIN

INTERNAL
DRAIN

EXTERNAL
DRAIN

INTERNAL
DRAIN

EXTERNAL
DRAIN

CONTINUOUS DOWNWARD SLOPE

UNIT

UNIT

UNIT

DO NOT EXTERNALLY
TRAP THE UNIT

DO NOT EXTERNALLY
TRAP THE UNIT

DPN001556