Piping Schematics

101

Figure 76 Primary connection locations—upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all

compressor models

Point

Description

X

in. (mm)

Y

in. (mm)

Connection Size / Opening

in. (mm)

W1

Water/Glycol/GLYCOOL Access (Bottom)

79-15/16 (2030)

9 (229)

3-1/2 x 8 (89 x 203)

W2

Water/Glycol/GLYCOOL Access (Top)

79-15/16 (2030)

9 (229)

3-1/2 x 8 (89 x 203)

W3

Water/Glycol/GLYCOOL Access (Side)

6 x 17-3/16 (152 x 437)

WS

Water/Glycol/GLYCOOL Supply

1-5/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

1-5/8 Cu Sweat

CGD

Condensate Gravity Drain

3/4 FPT

CPD

Condensate Pump Discharge (Opt)

56-1/4 (1429)

11-1/8 (282)

1/2 Cu Sweat

HUM

Humidifier Supply Line

56-1/4 (1429)

9-1/8 (232)

1/4 Cu Sweat

ECS**

Econ-O-Coil Supply

56 (1423)

7-5/16 (186)

1-5/8 Cu Sweat

ECR**

Econ-O-Coil Return

56 (1423)

4-1/2 (114)

1-5/8 Cu Sweat

E1

Electrical Connection (High Voltage)

52-3/8 (1330)

30 (762)

2-1/2

E2

Electrical Connection (High Voltage)

46-7/8 (1191)

30 (762)

2-1/2

LV1

Electrical Connection (Low Voltage)

19-1/2 (495)

29-1/16 (738)

7/8

LV2

Electrical Connection (Low Voltage)

19-1/2 (495)

30-1/2 (775)

7/8

LV3

Electrical Connection (Low Voltage)

19-1/2 (495)

31-15/16 (811)

7/8

* Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with
all local codes.
** Supplied on Dual-Cool systems only (4-pipe system)

NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions is ± 1/2" (13mm).
3. Field-routed alternatives for water/glycol connections.
4. See submittal page DPN001120 for blower outlet
and deck dimensional data.

All dimensions
from rear corner
of unit including
panels

X

0

Y

3-7/8"

(98mm)

14-1/4"

(362mm)

15-7/8"

(403mm)

Left Side Section View

Front Section View

(Left Front Panel Not Shown)

Top View of Unit

6"

(152mm)

17-3/16"

(437mm)

W3
WS

CGD*

CGD*

DPN001179
Rev. 2

WR

Front

E1

W1,

E2

LV1

LV2

LV3

W2

8"

(203mm)

ECS

ECR

HUM

Blower

Outlet

CPD

4

3

2-7/8"

(73mm)

86"

(2184mm)

3-1/2"

(89mm)

35"

(889mm)

3

3

3

3

3

3