Liebert heat rejection, Liebert ds unit (and associated piping) – Liebert Precision Cooling System DS User Manual

Page 97

Advertising
background image

Piping Schematics

87

Figure 62 Piping schematic—GLYCOOL with scroll compressor models

3-Way
Chilled Glycol
Valve

3-Way
Chilled Glycol
Valve

NOTE: Schematic representation shown. This schematic does not imply or define elevations and
component location, unless specifically noted.

Service

Valve

* Components are not supplied by
Liebert but are recommended for
proper circuit operation and
maintenance
** Field installed at highest point in
system on return line to pumps
*** Locate at tops of all risers and
any intermediate system high points

External
Equalizer

Sensing Bulb

NOTE: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.

FIELD PIPING
FACTORY PIPING

EVAPORATOR
COIL

Expansion
Valve

COMPRESSOR

LIQUID

SUCTION

Sight
Glass

Solenoid
Valve

Filter Dryer

DPN000898
REV 3

Paradenser
Condenser

To Second

Refrigeration

Circuit

Hose
Bib*

Hose
Bib*

Shutoff Valve*

Shutoff Valve*

Shutoff Valve*

Shutoff Valve*

Flow-Regulating
Valve*

Flow Switch
Supplied with Dual
Pump Systems

Pressure Port*

Gate Valves*

Check Valves*
(on Dual Pump
Systems only)

GLYCOL PUMPS

EXPANSION
TANK**

Hose
Bib*

ECON-O-COIL

LIEBERT
HEAT REJECTION

DRYCOOLER
(Glycol)

Aquastat
Sensing
Bulbs

Pressure
Port*

3-Way
Regulating
Valve

Sensor

Air Vents
(typical)***

LIEBERT DS UNIT

(and associated piping)

RETURN

RETURN

SUPPLY

SUPPLY

Relief valve(s) supplied
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar).

Thermistor

DISCHARGE

SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE

SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE

Check
Valve

Optional Dual Pump System shown

®

For systems with drycoolers,

refer to 12.11.3 - Drycooler Settings.