Table 51, Piping data—upflow, air-cooled 105kw (30 ton), all, Top view of unit – Liebert Precision Cooling System DS User Manual

Page 115

Advertising
background image

Piping Schematics

105

Figure 80 Primary connection locations—upflow, air-cooled, 105kW (30 ton), all

Table 51

Piping data—upflow, air-cooled 105kW (30 ton), all

Point Description

X

Y

Connection Size / Opening

R1

Refrigerant Access (Top)

106-7/8 (2715)

1-7/8 (48)

22-1/2 x 15-3/16 (572 x 386)

R2

Refrigerant Access (Bottom)

109-1/8 (2772)

13-7/8 (352)

16-7/16 x 4 (418 x 102)

L1

Liquid Line System 1

121-3/4 (3092)

16-3/4 (425)

5/8 Cu Sweat

L2

Liquid Line System 2

118-1/8 (3000)

16-3/4 (425)

5/8 Cu Sweat

G1

Hot Gas Discharge 1

118-1/4 (3004)

14-1/4 (362)

1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

115-5/8 (2937)

14-1/4 (362)

1-1/8 Cu Sweat

R3

Refrigerant Access (Side)

-

-

6 x 17-3/16 (152 x 437)

CGD* Condensate Gravity Drain

-

-

3/4 FPT

CPD

Condensate Pump Discharge (Opt)

102-3/8 (2600)

13-5/8 (346)

1/2 Cu Sweat

HUM

Humidifier Supply Line

101-1/8 (2569)

13-1/8 (333)

1/4 Cu Sweat

ECS

Econ-O-Coil Supply

101-1/8 (2569)

10-1/4 (260)

2-5/8 Cu Sweat

ECR

Econ-O-Coil Return

101-1/8 (2569)

5-1/4 (133)

2-5/8 Cu Sweat

E1

Electrical Conn. (High Volt)

98-1/2 (2502)

30 (762)

2-1/2

E2

Electrical Conn. (High Volt)

93 (2362)

30 (762)

2-1/2

LV1

Electrical Conn. (Low Volt)

41-1/8 (1045)

30-3/8 (772)

7/8

LV2

Electrical Conn. (Low Volt)

38-7/8 (987)

30-3/8 (772)

7/8

LV3

Electrical Conn. (Low Volt)

35-1/8 (892)

30-3/8 (772)

7/8

LV4

Electrical Conn. (Low Volt)

31-5/8 (803)

30-3/8 (772)

7/8

* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not

trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.

TOP VIEW OF UNIT

LV1

LV2

LV3

LV4

E1 E2

X

O

ECS

ECR

HUM

CPD

Blower

Outlet

Blower

Outlet

Blower

Outlet

L1 L2

G1 G2

R2

CGD*

6"

(152mm)

20-1/16"

(509mm)

R3

Factory Location

FRONT SECTION VIEW OF UNIT

(Left Front Panel Not Shown)

LEFT SIDE SECTION VIEW OF UNIT

All dimensions from
rear corner of unit
including panels

Front Of Unit

DPN001257
Rev. 0

Y

3-7/8"

(98mm)

17-3/16"

(437mm)

CGD*

15-7/8"

(403mm)

16-7/16"

(418mm)

22-1/2"

(572mm)

15-3/16"

(386mm)

4"

(102mm)

14-1/4"

(362mm)

35"

(889mm)

132"

(3353mm)

NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions

is ± 1/2" (13mm).

3. Field routed alternatives for refrigerant

gas and liquid line connection points.

4. See submittal page DPN001192 for

blower outlet and deck dimensional data.

3

3

3