3 drycooler settings, Table 59 aquastat settings-six-fan drycoolers, Table 60 aquastat settings-eight-fan drycoolers – Liebert Precision Cooling System DS User Manual

Page 131: Table 57, Table 58, Table 59, Aquastat settings—six-fan drycoolers, Table 60, Aquastat settings—eight-fan drycoolers, See tables 58

Advertising
background image

Maintenance

121

12.11.3Drycooler Settings

Applications with the Optional Stat Setting require field piping to be insulated to prevent condensa-

tion. Table 57 shows acceptable applications where stats must be adjusted to Optional Setting. Aqu-

astats must be field-adjusted to Optional Setting for:

• GLYCOOL/Dual Cool applications
• Single Drycooler loops with motor ball valve flow controls (motor ball valves are used on all Lie-

bert DS units with digital compressors). These units have a “D” or “G” in the seventh character:

DS/VS/xxxxD or DS/VS/xxxxG.

Table 57

Water/glycol system conditions requiring optional settings for aquastats

Cooling Type

Glycool

Glycol

Flow Control

MBV

WRV

MBV

WRV

Drycoolers in Loop

1

Multiple

1

Multiple

1

Multiple

1

Multiple

Stat Setting*

Optional

Optional

Optional

Optional

Optional

Factory

Factory

Factory

Insulate Field Piping

Yes

Yes

Yes

Yes

Yes

No

No

No

* See Tables 58 through 60
MBV=motor ball valve; WRV=water regulating valve

Table 58

Aquastat settings—two-fan through four-fan drycoolers

Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close

Aquastat #

Fans

Factory Setting

(Glycol) (see Notes 1 and 2)

Optional Setting

(GLYCOOL) (see Note 3)

AQ1

F1

65°F (18.3°C)

35°F (1.7°C)

AQ2

F2 & F3

75°F (23.9°C)

45°F (7.2°C)

AQ3

F4

70°F (21.1°C)

40°F (4.4°C)

Table 59

Aquastat settings—six-fan drycoolers

Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close

Aquastat #

Fans

Stat Location

Cabinet

Factory Setting

(Glycol) (see Notes 1 and 2)

Optional Setting

(GLYCOOL) (see Note 3)

AQ1

F1

Main

65°F (18.3°C)

35°F (1.7°C)

AQ2

F2

Main

70°F (21.1°C)

40°F (4.4°C)

AQ3

F3 & F4

Auxiliary

73°F (22.8°C)

43°F (6.1°C)

AQ4

F5 & F6

Auxiliary

75°F (23.9°C)

45°F (7.2°C)

Table 60

Aquastat settings—eight-fan drycoolers

Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close

Aquastat #

Fans

Stat Location

Cabinet

Factory Setting

(Glycol) (see Notes 1 and 2)

Optional Setting

(GLYCOOL) (see Note 3)

AQ1

F1

Main

65°F (18.3°C)

35°F (1.7°C)

AQ2

F2

Main

70°F (21.1°C)

40°F (4.4°C)

AQ3

F3 & F4

Auxiliary

73°F (22.8°C)

43°F (6.1°C)

AQ4

F5 & F6

Auxiliary

75°F (23.9°C)

45°F (7.2°C)

AQ5

F7 & F8

Main

78°F (25.6°C)

48°F (8.9°C)

NOTE
1. All drycoolers are shipped at Factory Setting.
2. Factory Setting is used for all glycol applications, except single drycooler loops with motor

ball valve controls.

3. Stats must be field-adjusted to Optional Setting for GLYCOOL/Dual Cool applications

and all single drycooler loops using motor ball valve flow controls.