Figure 8, 42kw (8-12 ton), all compressor models, Table 5 – Liebert Precision Cooling System DS User Manual

Page 23

Advertising
background image

Liebert DS Dimensions and Weights

13

Figure 8

Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton),
all compressor models

Table 5

Weights for downflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models

Compressor Type

Dry Weight - lb. (kg),

Approximate

Model

028, 035, 042

Semi-Hermetic Compressor

Water/Glycol

1930 (877)

GLYCOOL/Dual-Cool

2080 (945)

Scroll or Digital Scroll Compressor

Water/Glycol

1780 (809)

GLYCOOL/Dual-Cool

1930 (877)

33"

(838mm)

Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.

Front View

Top View

Air Inlet Opening

Shaded area indicates a
recommended minimum
clearance for component
access.

86"

(2184mm)

DPN000894
Rev. 3

2"

(51mm)

85" (2159mm)

76"

(1930mm)

35"

(889mm)

56-7/8"

(1445mm)

Opening

3/4"

(19mm)

Bezels

Secondary Entrance

High Volt Connection(s)

Condenser Cleanout Access

Secondary Entrance
Low Volt Connections

24-3/8"

(619mm)

Opening

15"

(381mm)

24"

(610mm)

Required for

condenser cleanout

Minimum required

for filter replacement

34" (864mm)

Secondary Condenser
Fluid Piping Entrance