12.10 Paradenser—Water-Cooled Condenser

During normal Paradenser operation, deposits will collect on inside wall of condenser tubes. It must

be cleaned periodically to ensure proper operation. Frequency of cleaning must be locally established

because it varies according to Paradenser usage and local fluid quality. See 12.9 - Facility Fluid and

Piping Maintenance.

12.10.1 Cleaning Instructions

Refer to Figure 1 - Downflow model component locations.
1. Disconnect power to unit.
2. Close field-installed isolation valves to isolate this unit’s condenser system from facility water or

glycol circuit.

3. Remove access panel from front of compressor section.
4. Locate the 1/2" NPT drain plugs located at lower front of compressor section and provide means to

collect fluid drained from system

5. Remove the 1/2" drain plugs using two wrenches to prevent damage to drain lines.
6. Locate and remove the 3" diameter clean out plugs on top of shell assemblies (use

Craftsman™ 1-3/16" drag link socket, Sears item # 00944514000 or similar).

7. Brush and flush each of the nominal 5/8" inner diameter, rifled copper tubes. Recommend using

John R. Robinson, Inc. or similar:

• Motorized Tube Cleaner, Model JR3800-1200
• Nylon brush 9/16" diameter, Model JRRB211N-916
• Flexible shaft, Model JRRFS702-25

8. Reinstall 1/2" drain plugs 6 to 7 turns using Loctite 567 PST Thread Sealant as instructed by the

manufacturer.

9. Wipe clean the machine threads and sealing surfaces of 3" diameter clean out plugs.
10. Remove and install new O-rings (Liebert part number 180750P1) on the 3" diameter clean out

plugs. (Do not use thread sealant).

11. Hand tighten 3" diameter clean out plugs and torque using drag link socket to 25 ft-lb.
12. Leak check fluid system (refer to Leak Checking of Unit and Field Piping on page 75).
13. Bleed system using Schrader ports near the top of the Paradenser.
14. Ensure that condensing fluid isolation valves are fully open.
15. Unit is ready to be put on-line.

12.11 Water/Glycol Control Valves

12.11.1Regulating Valves – Semi Hermetic and Standard Scroll Compressors

The water regulating valves automatically regulate the amount of fluid necessary to remove the heat

from the refrigeration system, permitting more water to flow when load conditions are high and less

fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve

seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.

Adjustment—Johnson Controls/Penn Johnson Valves

The valves may be adjusted with a standard refrigeration service valve wrench or screwdriver.
Table 56

Recommended refrigerant pressures

System Design

PSIG (kPa)

Water-Cooled

65 to 75°F water (18 to 24°C)

210 (1450)

85°F water (29°C)

225 (1550)

Glycol-Cooled

295 (2035)

Maximum

330 (2275)

High Pressure Cut-out

400 (2859)