Models, Table 33 – Liebert Precision Cooling System DS User Manual

Page 63

Advertising
background image

Disassembling the Liebert DS for Transport

53

Figure 43 Component dimensions—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressor

models

Table 33

Component weights—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressors

Component

Dry Weight, lb (kg) Approximate (Includes Panels)

Air Cooled

Dual Cool

Compressor Assembly

950 (432)

950 (432)

Filter & Electric Box Assembly

270 (123)

270 (123)

Blower & Coil Assembly

1820 (827)

2180 (991)

37"

(940mm)

59-7/16"

(1510mm)

DPN001057
Rev. 0

131" (3327mm)

Assembled Length

33"

(838mm)

26"

(660mm)

105"

(2667mm)

76"

(1930mm)

39"

(991mm)

41-11/16"

(1059mm)

Filter and Electric Box Assembly

Compressor Assembly

Blower and Coil Assembly

76"

1930mm

Assembled

Height

Advertising