All compressor models – Liebert Precision Cooling System DS User Manual

Page 106

Advertising
background image

Piping Schematics

96

Figure 71 Primary connection locations—downflow, water/glycol/GLYCOO,L 53-77kW (15-22 ton), all

compressor models

Point)

Description)

X

inches (mm)

Y

inches (mm)

Connection Size / Opening

inches (mm)

W

Water/Glycol/GLYCOOL Access

103 (2616)

9 (229)

3-1/2 x 8 (89 x 203)

WS

Water/Glycol/GLYCOOL Supply

104-3/4 (2661)

11 (279)

2-1/8 Cu Sweat

WR

Water/Glycol/GLYCOOL Return

104-3/4 (2661)

15 (381)

2-1/8 Cu Sweat

CD

Condensate Drain *

69-1/4 (1759)

30 (762)

3/4 FPT

W/ Optional Pump

69-1/4 (1759)

30 (762)

1/2 Cu Sweat

HUM

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

ECS**

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

ECR**

Econ-O-Coil Return

72 (1829)

29 (737)

2-1/8 Cu Sweat

HS

Hot Water Reheat Supply

Consult Factory

HR

Hot Water Reheat Return

Consult Factory

E1

Electrical Connection (High Volt)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Connection (High Volt)

75-3/8 (1915)

31-1/8 (790)

2-1/2

LV1

Electrical Connection (Low Volt)

1-7/8 (48)

28-1/2 (724)

7/8

LV2

Electrical Connection (Low Volt)

1-7/8 (48)

30-1/4 (768)

7/8

LV3

Electrical Connection (Low Volt)

1-7/8 (48)

32 (813)

7/8

B1

Blower Outlet (15 x 15)

23-1/8 (587)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

Blower Outlet (15 x 11)

27-3/4 (705)

18-1/16 (459)

14-3/4 x16-1/16 (375 x 408)

B2

Blower Outlet (15 x 15)

50-3/8 (1280)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

Blower Outlet (15 x 11)

54-3/8 (1381)

18-1/16 (459)

14-3/4 x16-1/16 (375 x 408)

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do

not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.

** Supplied on Dual-Cool systems only (4-pipe system)

3-1/2"

(89mm)

Blower

Outlet

Section A-A

Front View

16-1/16"

(408mm)

B2

A

A

X

Y

O

Tolerance on all
piping dimensions
is ± 1/2" (13mm)

109"

(2769mm)

Front of Unit

Note: Drawing not to scale

DPN000933
Rev. 2

W

8" (203mm)

WS

WR

LV3

LV2

LV1

ECS

HUM

CD

ECR

E1 E2

B1

Blower

Outlet

35"

(889mm)

All dimensions
from rear corner
of unit including
panels