2 installation and connection – GE Industrial Solutions AF-300 C11 User Manual

Page 17

Advertising
background image

-15-

AF-300C11

4”
(10 cm)

4”
(10 cm)

0.4”
(1 cm)

0.4”
(1 cm)

2 Installation and Connection

2-1

Operating Environment

Install this product at a place satisfying the conditions listed in Table 2-1-1.

Table 2-1-1 Operating environment

Item

Specifications

Place

Indoor

Ambient

temperature

-10 to +50 °C (+14 to +122°F)

Ambient relative

humidity

5 to 95%RH(No condensation allowed)

Atmosphere

The product must not be exposed to dust, direct sunlight, corro-

sive gas, inflammable gas, oil mist, vapor, or water drops.

There must be no salt in the atmosphere.

Condensation must not be caused by sudden changes in tem-

perature.

Altitude

3300 feet (1000m) or less ( Air pressure : 86kPa to 106kPa )

Vibration

3mm:

2 to less than 9Hz

9.8 m/s

2

:

9 to less than 20Hz

2 m/s

2

:

20 to less than 55Hz

1 m/s

2

:

55 to less than 200Hz

2-2

Installation Method

¬ Tightly fasten the product in the upright position on a strong structure using four bolts (M4) with the

characters AF-300C11 facing the front. Be sure not

to turn the product upside down, and install it on a

horizontal surface.

- Heat is generated while the drive is operating, so the

gaps shown in Figure 2-2-1 are necessary for the

passage of cooling air. The generated heat is

radiated upward by the built-in cooling fan, so do not

install this product below a device that is sensitive to

heat.

® The temperature of the heat sink increases to about

90 °C while the drive is operating. Therefore, the

surface behind where the product is located must be

able to withstand this temperature increase.

!

WARNING

Install this product on a nonflammable material such as metal,

otherwise fire could occur.

¯ When installing this product in a control panel, carefully consider the ventilation to prevent the am-

bient temperature of the drive from exceeding the specified value. Do not install it in a hermetically
sealed box from which heat is not radiated fully.

0.4”
(1 cm)

Figure 2-2-1 Installation direction and
surrounding space

Advertising