7 Troubleshooting

7-1

In case of tripping

In the event the drive tripping, diagnose by the help of the alarm display as shown below.

(1) Overcurrent (OC)

Overcurrent dur-
ing acceleration
OC1

Overcurrent during
deceleration OC2

Overcurrent while run-
ning at constant speed
OC3

Remove short-circuit
or ground.

Reduce load or expand
drive capacity.

Torque boost amount
correct?

Has load changed
suddenly?

Deceleration time
setting too short
compared with load?

Faulty drive or error
because of noise. Co n-
tact GE Fuji.

Reduce torque
boost amount.

Acceleration time
setting too short
compared with load?

No

No

No

yes

yes

yes

yes

yes

yes

yes

yes

yes

Can the deceleration
time setting be pro-
longed?

Prolong time setting.

Prolong time set-
ting.

Can the acceleration
time setting be pro-
longed?

Braking method
needs investigation.
Consult with GE Fuji.

Reduce load or ex-
pand drive capacity.

Suppress load fluctuation
or expand drive capacity.

Are the motor connecting terminal (U,V,W) short-circuited or
grounded?

No

No

No

No

No

No

No

No

Load excessive?

Can torque boost
amount be re-
duced?

No