-72-

Check part

Check item

How to inspect

Evaluation criteria

Resistor

1)Unpleasant smell and crazing
of the insulation by
overheating
2)No open circuit?

1)Olfactory and
visual inspection
2)Visual inspection
or use a multimeter
by removing a
connection on one
side.

1)Not abnormal.
2)Less than about ±10% of
the indicated
resistance value

Trans-
former and
reactor

Abnormal buzzing or unpleasant
smell?

Aural, olfactory, and
visual inspection

Not abnormal.

Main circuit

Magnetic
contactor
and relay

1)Rattling when operating?
2)Roughness of contact?

1)Aural
2)Visual inspection

1), 2) Not abnormal.

Control circuit

Control PC
board and
connector

1)Loose screws or connectors?
2)Unpleasant smell or
discoloration?
3)Cracks, damage, deformation, or
excessive rust?
4)Electrolyte leakage or a
deformed mark on the
capacitor?

1)Tighten more.
2)Olfactory and
visual inspection
3),4)Visual
inspection

1), 2), 3), 4)
Not abnormal.

Cooling
fan
(2 HP or
more)

1)Abnormal sound or vibration?
2)Loose of bolts?
3)Discoloration by
overheating?

1)Aural and visual in-
spection. Turn with
hand. (Make sure power
is off)
2)Tighten more
3)Visual inspection

1)The fan must rotate
smoothly.
2), 3)Not abnormal

Cooling system

Ventilation
way

Clogging-up or foreign substance on
heat sink or intake/exhaust ports?

Visual inspection

Not abnormal

(Note) Use a capacitance measuring instrument available on the market which is easy to use.

(Remark) If the equipment is stained, wipe it with a cleaning cloth, which is chemically neutral.

Vacuum-clean the dust.

Advertising