This function displays the integration time of power supply applied to the drive.

0 to 655 are displayed to indicate 0 to 65500 hours.

If the integration time exceeds 65500 hours, 65500 is displayed continuously. While the total of power

supply times is less than one hour, the times are not integrated.

Trip history

This function memorizes the history of the last four protection operations.

Each data item can be called using the

key.

The calling procedure is shown below:

No.

Procedure

Display ex-

ample

Remarks

1

Call H 0

2

H 0

2

2

O U 2

The contents (history) of the latest

alarm are displayed.

3

O H 2

The contents of the second latest alarm

are displayed.

4

O C

1

The contents of the third latest alarm

are displayed.

5

Press the

FUNC
DATA

key

Press the

key

Press the

key

Press the

key

Press the

key

Press the

key

Press the

key

Press the

key

-

-

-

The contents of the fourth latest alarm

are displayed. (This example is for no

history.)

6

Press the

key

E n

d


The contents of a new alarm is stored in the data area for the history of the latest alarm. At this time, the
history of the latest alarm is stored in the data area for the second latest alarm. The histories of the second
and third latest alarms are moved in this way and the history of the fourth latest alarm is deleted.
Stored trip histories are not deleted although data initialization is executed with H03.