Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-35-

FUNC

DATA

Func-

tion

code

No.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

E01

X1 terminal function

-

-

0

N

E02

X2 terminal function

-

-

2

N

E03

X3 terminal function

Use the code values listed below to se-
lect [

X1],

[

X2]

and [

X3]

terminal func-

tions.

-

-

3

N

0: Multistep frequency 1 (SS1)

1: Multistep frequency 2 (SS2)

2: Coast-to-stop command (BX)

3: Alarm reset (RST)

4: External alarm (THR)

5: Write enable command for keypad
(WE-KP)

6: PID control cancel (Hz/PID)

7: Link operation selection (LE)

Func-

tion

code

No.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

C01

Jump frequency 1

0 to 120Hz

Hz

1

0

Y

C02

2

1

0

Y

C03

3

1

0

Y

C04

(Hysteresis)

0 to 30Hz

Hz

1

3

Y

C05

Multistep frequency 1

0.0 to 120Hz

Hz

0.1

0.0

Y

C06

2

0.1

0.0

Y

C07

3

0.1

0.0

Y

E: Extension Terminal Functions

C: Control Functions of Frequency