GE Industrial Solutions AF-300 C11 User Manual

Page 59

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-57-

FUNC

DATA

PID control

(Feedback signal)

This function selects a PID control feedback signal.

0 Terminal 12

(0 to +10Vdc)

1

Terminal C1

(4 to 20mAdc)

2

Terminal 12

(+1 to +5Vdc)

PID control (P-gain)

This function sets a P-gain.

0. 0 1 to 1 0. 0 P-gain from 0.01 to 10.0 times (1 to 1000%) (in increment of 0.01 step)




PID control (I-gain)

This function sets an integral time.

0. 0 : No integration

0. 1 to 9 9 9 : Integral time 0.1 to 999s

(in 0.1s step for 99.9s or less, 1s step for 100s or more)

PID control (D-gain)

This function sets a derivative time.

0. 0 0 : No derivative

0. 0 1 to 1 0. 0 : Derivative time 0.01 to 10.0s (in 0.01s step)

PID control
(Feedback filter)

This function sets a filter time constant of PID feedback.

0. 0 to 6 0. 0 : Time constants 0.0 to 60.0s (in 0.1s step)

Factory

setting

Change during

operation

1

N

H21

H24

H25

H22

H23

Factory

setting

Change during

operation

0.01

Y

Factory

setting

Change during

operation

0.0s

Y

Factory

setting

Change during

operation

0.00s

Y

Factory

setting

Change during

operation

0.5s

Y

Advertising