background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-50-

FUNC

DATA

Motor

sound

(sound tone)

This function adjusts the motor operation sound when a value of 7 or less is set with function F26.

0

Level 0

to

3

Level 3

FM terminal (voltage adjust)

This function regulates the frequency meter voltage level output to the FM terminal in the range from 0
to 200% (in 1% step).

0 (

Full scale about 0Vdc

)

to

2

0

0

(

Full scale about 11Vdc

)

FM terminal (Function)

This function selects the contents of output to the FM terminal.

0

Output frequency (maximum output frequency = 100%)

1

Output current (drive rated current x 2 = 100%)

2

PID feedback value (full scale = 100%)

3

DC link circuit voltage (500Vdc = 100%)

11V 200%

Note : Output to the FM terminal is pulse output

with constant frequency and variable duty.

Variable

Approx. 13V

50% 100%

Output/full scale

Fixed to 121.6Hz

Output

voltage

F27

F31

Factory

setting

Change during

operation

0

Y*

F30

Factory

setting

Change during

operation

100%

Y

Factory

setting

Change during

operation

0

Y

5V

50%

100%

10V