Starting frequency stop frequency, Motor sound, Carrier freq.) – GE Industrial Solutions AF-300 C11 User Manual

Page 51: F26 f24, F23 f25

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-49-

FUNC

DATA


Starting frequency


Stop frequency

These functions set a starting or stop frequency in a range

from 1 to 6Hz in 1Hz step.

1

1Hz

to

6

6Hz




Data cannot be
changed.



Motor sound

(carrier freq.)

This function changes the motor tone quality by changing the carrier frequency.

0

to

Choose among 16 types according to the usage conditions.

1 5

Data code

0 : 0.75kHz (

Low carrier

)

1 : 1kHz

2 : 2kHz

15 : 10kHz (

High carrier, low noise)

Note: When the drive is operating at 9kHz or higher carrier frequency, the carrier

frequency for may be reduced to 8kHz automatically to protect the drive.

Starting frequency stop frequency



Starting
frequency setting
Stop
frequency setting


t

Output frequency in forward/

reverse operation


0.2Hz

Stop frequency setting

Starting frequency setting


Starting frequency setting

Stop frequency setting

FWD


REV

Starting frequency < stop frequency


Stop
frequency setting
Starting
frequency setting

t

If the set frequency is lower than the stop frequency,
the drive output is 0Hz.

F26

F24

Factory

setting

Change during

operation

0.0

-

F23

F25

Factory

setting

Change during

Operation

1Hz

N

F23
F25

1Hz

N

Factory

setting

Change during

operation

2kHz

Y