Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-56-

FUNC

DATA

Data initialization

This function initializes data items set with all functions to values set in the factory.

0

Manually set value

1

Initialized (factory set value )

The display is changed from

0

to

1

when the

STOP

and

keys are pressed simultane-

ously.

When the

FUNC
DATA

key is pressed under this condition, initial data is written and a frequency set by the

built-in POT (VR) is displayed automatically.

Auto Reset

This function selects a retry operation if the drive is tripped.

0

:

Inactive

to

1

:

The auto reset count is fixed to 5 and auto reset starts when 0.5s elapses after tripping .

Auto reset is attempted only for an overcurrent/overvoltage trip that occurs during operation.



Fan stop operation

0 :

ON-OFF No control (always on)

1

:

ON-OFF Control

(The fan is turned off when the drive temperature becomes low after operation is

stopped.)


PID control (Mode select)

0

:

Inactive

1

:

Active (Normal)

2

:

Active (Inverse)

The feedback signal value (%) is displayed by assuming the full scale to be 100% when a PID control
operation is selected.

Factory

setting

Change during

operation

0

N

H20

Factory

setting

Change during

operation

0

N

H03

Factory

setting

Change during

operation

0

Y*

H04

H06

Factory

setting

Change during

operation

0

Y*

Select a PID control operation.