GE Industrial Solutions AF-300 C11 User Manual

Page 36

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-34-

FUNC

DATA

Func-

tion

code

No

.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

F10

Electronic thermal
overload relay (Select)

0:Inactive

1:Active
(for 4-pole standard motor)

2:Active
(for 4-pole forced air motor)

-

-

1

Y*

F11

(Level)

20 to 135% of drive rated current

A

0.01

Typical

value of

GE 4-

pole

motor

Y*

F12

(Thermal time constant)

0.5 to 10.0min

min

0.1

5.0

Y*

F14

Restart after mo-
mentary power failure

0:Inactive (Trip and alarm when
power failure occurs)

1:Inactive (Trip and alarm when
power recovers)

2:Active (Momentarily stops and
restarts at setting frequency of
before power failure)

3:Active (Momentarily stops and
restarts at starting frequency)

-

-

0

N

F15

Frequency limiter

(High)

0 to 120Hz

70

Y

F16

(Low)

0 to 120Hz

Hz

1

0

Y

F17

Gain (for frequency
setting signal)

0: For 0 to +10Vdc,
1: For 0 to +5Vdc

-

-

0

N

F18

Bias frequency

-120 to 120Hz

Hz

1

0

Y

F20

DC injection brake

(

Starting freq.

)

Fixed to 3Hz

Hz

-

3.0

-

F21

(Braking level)

0 to 100%

%

1

0

Y

F22

(

Braking time

)

0.0 s (Inactive), 0.1 to 30.0 s

s

0.1

0.0

Y

F23

Starting frequency

1 to 6Hz

Hz

1

1

N

F24

-

Data cannot be changed.

-

-

0.0

-

F25

Stop frequency

1 to 6Hz

Hz

1

1

N

F26

0 to 15kHz
0.75kHz is set when 0 is specified

kHz

1

2

Y

F27

Motor sound
(carrier freq.)

(sound tone )

0: Level 0 1: Level 1
2: Level 2 3: Level 3

-

-

0

Y

F30

FM terminal

(

Voltage adjust

)

0 to 200%

%

1

100

Y

F31

(

Function

)

0: Output frequency
1: Output current
2: PID feedback amount
3: DC link circuit voltage

-

-

0

Y*

F36

30Ry operation mode

0: Excited when tripped
1: Normally excited

-

-

0

N