GE Industrial Solutions AF-300 C11 User Manual

Page 45

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-43-

FUNC

DATA


Torque boost

This function can choose between 32 types of boost according to the load type and motor characteris-
tics.

0

to

1

2

Lower

to

3

1

Higher




Electronic thermal O/L relay (Select)

This function is used to select between the following three values:

0

Inactive

1

Active

· · · · · · · · · · · ·

4-pole standard motor

2

Active

· · · · · · · · · · · ·

4-pole forced air motor

Electronic thermal O/L relay(Level)

0. 1 4

to

2 2. 3

Set the value obtained by multiplying the motor rated current by coefficient K in the table below ac-
cording to the wiring length between the drive and motor.


Wiring length

Drive HP

0’ 132’ 165’ Max. 330’

1/8

K=1.2

External thermal is
recommended.

1/4

K=1

K=1.1

1/ 2 to 5

K=1

F10

F11

This function sets the operation level of an electronic thermal O/L relay by using an
ampere value according to the motor rated current.
20 to 135% of the drive rated current can be set.
Values less than 9.99A can be set in 0.01A step and values more than 10.0A can be set
in 0.1A step.

For square law torque loads
(fan, pump)

F09

Output

voltage

Output frequency

Higher

Lower

Square law torque

Factory setting

Change during

operation

Motor rated

Y*

Factory

setting

Change during

operation

13

Y

Factory

setting

Change during

operation

1

Y*