Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-53-

FUNC

DATA

7

Link operation selection (LE)

Operation setting can be done by commands from RS485 when the LE terminal

is connected to the CM terminal.

A command from RS485 is ignored when the LE terminal is disconnected from

the CM terminal.

ON input is assumed when LE is not selected.

LE is valid only when function

o 0 0

is set to

1

(option operation).

Note: Set function

E 0 3

to a value from

0

to

3

when using the X3 terminal

as a PLC terminal (SW7 is set to PLC).


Continued from previous page