GE Industrial Solutions AF-300 C11 User Manual

Page 54

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-52-

FUNC

DATA

X1 terminal function

X2 terminal function

X3 terminal function

0

Multistep frequency selection 1 (SS1)

1

Multistep frequency selection 2 (SS2)

f1 :

Frequency selected with F01

(keypad panel/analog/freq. setting POT )

f2 :

Frequency selected with C05

f3 :

Frequency selected with C06

f4 :

Frequency selected with C07

OFF input is assumed if SS1 or SS2 is not selected.

2

Coast-to-stop command

Drive output is cut when the BX terminal is connected to the CM terminal.

OFF input is assumed when BX is not selected.

3

Alarm reset (RST)

The alarm output is released between the RST and CM terminals when power is turned on.
The trip status is released between the RST and CM terminals when power is turned off.
(Refer to 6-2 Alarm Reset on page 60)

4

External alarm (THR)

Drive trips with OH2 when the THR terminal is disconnected from the CM
terminal.

ON input is assumed when THR is not selected.

5

Write enable command for keypad(WE-KP)

Function change from the keypad panel is disabled when the WE-KP terminal is disconnected
from the CM terminal.

Function change from the keypad panel is enabled when the WE-KP terminal is connected to the
CM terminal.

ON input is assumed when WE-KP is not selected.

6

PID control cancel (Hz/PID)

PID control operates when the Hz/PID terminal is disconnected from the CM
terminal and does not operate when they are connected.

OFF is assumed when the Hz/PID is not selected.

Hz/PID is valid only when function

H 2 0

is set to

1

or

2 .

(PID control operation).

f3

f2

f1

FWD-CM

ON


(SS1)-CM

ON ON

(SS2)-CM

ON

Factory

setting

Change during

operation

0

N


E01

2

N

E02

3

N

E03

E01

E02

E03

t

Output
frequency

f4