GE Industrial Solutions AF-300 C11 User Manual

Page 81

Advertising
background image

- 79 -

2) Single-phase 200V input series

Item

Specifications

Drive HP

1/8

1/4

1/2

1

2

3

Nominal applied motor
*1 (HP)

1/8

1/4

1/2

1

2

3

Rated output
capacity *2 (kVA)

0.28

0.56

1.0

1.6

2.8

4.0

Voltage(V)

3-phase, 200V/50Hz, 200, 220, 230V/60Hz (Proportional to input voltage)

Rated current (A)

0.7

1.4

2.5

4.0

7.0

10.0

Overload capacity

150% of rated current for 1 min.

Output ratings

Rated frequency (Hz)

50, 60Hz

Phases, Voltage, Fre-
quency

Single-phase 200 to 240V 50/60Hz

Voltage/frequency
variations

Voltage: +10% to –10%, Frequency: +5% to –5%

Capability for voltage
dip *3

When the input voltage drops 165V or more, the drive can be operated continuously.

When the input voltage drops below 165V from rated voltage, the drive can be operated
for 15ms.

1.2

2.0

3.5

6.5

11.8

17.7

Rated input current *6

(with DCR)

(without DCR)

2.3

3.9

6.4

11.4

19.8

28.5

Input power supply

Required power sup-
ply capacity *4 (kVA)

0.3

0.4

0.7

1.3

2.4

3.6

Braking torque
*5 (%)

150

100

50

30

Braking

DC injection
braking

Starting frequency: 3Hz(fixed), Braking current (0 to 100%),

Braking current ( 0 to 30%)

Protective structure
(IEC60529)

• Closed type IP20

Cooling method

• Self-cooling

• Fan cooling

Weight (Lb)

1.3

1.3

1.5

2.0

3.5

4.9

Notes:

*1 A 4-pole standard motor is assumed as a nominal applied motor.
*2 Drive output capacity (kVA) at 230V.
*3 When a momentary power failure occurs, while rated voltage is applied 85% of load of nominal motor is

given.

*4 When an optional power-factor correcting DC reactor is used.
*5 Average braking torque where an unloaded motor decelerates and stops from 60Hz

operation. (Varies according to the motor efficiency)

*6 The specification is calculated on assumption that the drive is connected to a 500 kVA-equivalent power

transformer.

*7 The inter-phase imbalance ratio (%) = ((Max. voltage) - (Min. voltage)) / (Average voltage among three

phases) x 67