5 selecting function – GE Industrial Solutions AF-300 C11 User Manual

Page 35

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-33-

FUNC

DATA

5 Selecting Function

5-1

Function Selection List

Table 5-1-1 Table of

Function Selection List

Func-

tion

code

No

.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

F00

Data protection

0: Data change enabled,
1: Data protected

-

-

0

N

F01

Frequency command

0:Key operation (

,

key)

1:Voltage input (terminal [12])
(0 to +10Vdc, 0 to +5Vdc)
2:Current input (terminal[C1])
(4 to 20mAdc)
3:Voltage input + current input
(terminals[12]+[C1])
4:Analog (VR built in drive)

-

-

4

N

F02

Operation method

0: Keypad operation
1: Terminal operation (STOP key active)
2: Terminal operation (STOP key inactive)
3: Terminal operation (STOP key active)

with GE software

4: Terminal operation (STOP key inactive)

with GE software

-

-

0

N

F03

Maximum output fre-
quency

50 to 120Hz

Hz

1

60

N

F04

Base frequency

25 to 120Hz

Hz

1

60

N

F05

0

F06

-

Data cannot be changed.

-

-

0

-

F07

Acceleration time

0.0 to 60.0s
0.01 second is set when 0.0 is specified.

s

0.1

6.0

Y

F08

Deceleration time

0.1 to 60.0s

s

0.1

6.0

Y

F09

Torque boost

0,1

:

Variable torque

characteristic

2 to 31: Constant torque
characteristic

-

1

13

Y

F: Fundamental functions

Advertising