GE Industrial Solutions AF-300 C11 User Manual

Page 60

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-58-

FUNC

DATA

In PID control, an output frequency is adjusted to a feedback value.

Use

F 0 1

to set a frequency and

H 2 1

to make the feedback value and the refer-

ence value equal.

Option selection
(RS485 RTU communication)

0

:

Option inactive

1

:

Option active

Always set

0

when the optional RS485

RTU

serial communication unit is not used.

If

1

is set, Er 8 occurs.

For explanations of “o01” to “o11”, refer to the instruction manual that comes with the

optional RS485 serial communication unit.

PID control

o00

Kp : P-gain Td : Derivative time Ti : Integral time

Output

frequency

Deviation

Normal

operation

Deviation is positive and
frequency increases.

Output

frequency

Deviation

Inverse

operation

Deviation is positive and
frequency decreases.

Td)

s

Ti

s

1

(1

Kp

+

+

Reference

frequency

Feedback value

(sensor)

_

+

Switching between

Normal and

Inverse operation

Drive

output

PID arithmetic unit

Deviation

IM

P

AF-300C11

Factory

setting

Change during

operation

0

Y*