Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-37-

FUNC

DATA


Function
code No.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

o00

RTU Option

0 : Inactive 1 : Active

-

-

0

Y*

o01

Address

1 to 247 (Max – 31 Drives)

1

Y*

o02

Mode select on no response
error

0 : Er8 by 8 times communiction/checksum

errors

1 : Er8 by 8 times communiction/checksum

errors

2 : Er8 with no communication more than

timer (o03)

3 : Retry and keep running

0

Y*

o03

Timer

1 to 60 s

s

1

2

Y*

o04

Baud rate

1 : 9600 2 : 4800

3: 2400

-

1

Y*

o05

Data length

0 : 8 bits (Fixed)

-

0

Y*

o06

Parity check

0 : No checking
1 : Even parity, 2 : Odd parity

-

0

Y*

o07

Stop bits

0 : 2bits 1 : 1bit
(Automatically changed by o06 setting)

-

0

Y*

o08

No response error detection
time

0 : (No detection)
1 to 60 s

s

1

0

Y*

o09

Response interval

0.00 to 1.00 s

s

0.1

0.01

Y*

o10

RTU Frequency Command 0 : F01 setting is active

1 : RTU setting is active

-

0

N

o11

RTU Operation Command 0 : F02 setting is active

1 : RTU setting is active

-

0

N

Note:

For details on “o01” to “o11”, refer to the instruction manual that came with the optional RS485 RTU

serial communication option.

O: Optional Functions