GE Industrial Solutions AF-300 C11 User Manual

Page 24

Advertising
background image

-22-

Classifi-

cation

Termi-
nal

symbol

Terminal name

Detailed specifications

Remarks

Analog

output

FM, 11 Analog monitor

Data selected between the following items is
output with DC voltage:

Output frequency
PID feedback value
Output current
DC link circuit voltage

* Up to two analog voltmeters (input imped-
ance : 10 k

can be connected.

Note: Output waveform: An AC pulse is out-
put with consistent frequency and variable
duty. The average DC voltage is proportional
to output frequency and output current (fre-
quency : 121.6 Hz).

Contact

output

30A
30B
30C

Alarm output for any
fault

If the drive is stopped with an alarm, the
non-voltage contact signal (SPDT) is output

(Contact rating: 250V ac, 0.3 A, Power factor
= 0.3)
(48V dc, 0.5A for Low-voltage Directive or
42V dc, 0.5A for UL/cUL)

Whether an alarm is generated with an excit-
ing operation or non-exciting operation can
be switched.



Optional

DX

+

DX

RS485 RTU commu-
nication input/output

Terminal for RS485 communication (when
option board is installed)

DX

+

: Non-inverted signal,

DX

: Inverted signal

Installed on op-
tional board.

Advertising