GE Industrial Solutions AF-300 C11 User Manual

Page 38

Advertising
background image

Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-36-

FUNC

DATA


Func-

tion

code

No.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

P00

Motor characteristics

0 to 10

-

-

2

Y



Func-

tion

code

No.

Name

Setting range

Unit

Min.

unit

Factory

setting

Change

during

operation

User

setting

H01

Operation time

Operation time accumulation

100Hr

1

0

-

H02

Trip history

The contents of the last four alarms are
displayed sequentially.

-

-

---

-

H03

Data initialization

1: Initialized
(return to factory setting value)

-

-

0

N

H04

Auto-reset

0: Inactive

1: Active (5 times fixed)

-

-

0

Y*

H06

Fan Stop Operation

0: Inactive

1: Active

-

-

0

Y*

H20

PID control

(

Mode select)

0: Inactive

1: Active (Normal operation)

2: Active (Inverse operation)

-

-

0

N

H21

(Feedback signal)

0:

Terminal

[12]

(0 to +10Vdc)

Input

1:

Terminal

[C1]

(4 to 20mAdc)

Input

2:

Terminal [

12]

(+1 to +5Vdc)

Input

-

-

1

N

H22

(

P-gain

)

0.01 to 10.0 times (1to1000%)

-

0.01

0.01

Y

H23

(

I-gain)

0.0s :

Inactive

0.1 to 999s

s

0.1

0.0

Y

H24

(D-gain)

0.00s :

Inactive

0.01 to 10.0s

s

0.01

0.00

Y

H25

(

Feedback filter)

0.0 to 60.0s

s

0.1

0.5

Y

H: High Performance Functions

P: Motor Parameters

Advertising