Change during operation: N = impossible, Y* = possible (enabled by using ), Y= possible (enabled by using

)

-54-

FUNC

DATA


Jump frequency 1, 2, 3

These functions jump frequencies to prevent overlap be-

tween the load mechanical resonance point and drive

output frequency.

Up to three jump points can be set.

These function do not operate when 0Hz is set.

No frequency is jumped during acceleration and decel-

eration.

If three continuous frequencies are set, the total of the

three jump widths is set as the jump width.

Jump frequency (Hysteresis)

This function sets a jump width in a range from 0 to 30Hz in 1Hz step.


Multistep frequency setting 1

Multistep frequency setting 2

Multistep frequency setting 3

These functions set a multistep frequency

setting

from 0 to 120Hz in 0.1Hz step (for 99.9 Hz or less) or

1Hz step (for 100Hz or more) by switching the external contact signal.

The ON and OFF of terminal function SS1/SS2 (see explanation of E01, E02, and E03) switches between

the frequencies set by these functions C05, C06, and C07.



Motor characteristics

This function removes abnormalities in the output current such as current vibration.

0

Current vibration is not suppressed.

to

1 0

Current vibration is minimized.







Jump
frequency

Jump
frequency

Jump
frequency

C05

C06

C07

C04

Factory

setting

Change during

operation

2

Y

P00

Jump width

Jump width

Jump width

C01

C02

C03

Frequency setting

Output Frequency

Factory

setting

Change during

operation

0.0Hz

Y


C01

0.0Hz

Y

C02

0.0Hz

Y

C03

Factory

setting

Change during

operation

3Hz

Y

Factory

setting

Change during

operation

0.0Hz

Y


C05

0.0Hz

Y

C06

0.0Hz

Y

C07