1. Press Measure S3 S3 S1 then the following text will be

displayed:

PERFORM ZERO-POINT CALIBRATION ?

NO YES

2. Follow the set-up of a combined zero-point and humidity-

interference calibration by following the black arrows in the

schematic diagram shown in

Fig.12.18

.

The following text will appear:

ZERO-POINT CALIB. CONNECT CLEAN, DRY AIR

AND PRESS ENTER WHEN READY

3. Refer to

section 12.6.2

for the practical details of a zero-point

calibration task.

When the zero-point calibration task is complete, the following text

appears on the screen:

HUM. INTERFERENCE. CONNECT CLEAN, DRY AIR

AND PRESS ENTER WHEN READY

4. Refer to

Section 12.7.2

for the practical details of a humidity-

interference calibration task.

12.11 Setting-up any Combined Calibration – Stand-

alone Use

Although we have separated the various calibration tasks and

described how to set them up and perform them alone, it is, of

course possible to set-up any combination of calibration tasks, for

example, that combining the zero-point and humidity-interference

calibration tasks described in

Section 12.11

.

After setting-up any combined calibration task, the Monitor responds

by telling you about which gas supply is required for each calibration

task.

When the combined calibration task is complete, the text

CALCULATING. PLEASE WAIT appears on the screen.

If any calibration data is uncertain or unacceptable an error message

(marked by an asterisk) will appear on the screen after the

calibration factors have been calculated. Whenever an asterisk is