Installation, Maintenance and Commissioning Manual :6877419 02/2013

Electrical Data – W2W2 Continued

SCD31D100-W2W2

SC31D120-W2W2

SC31D130-W2W2

Standard Dry Cooler Match

2 x DR70

2 x DR95

2 x DR95

Unit Data - W2W2

(1)

Nominal Run Amps

A

102.7

113.5

118.1

Maximum Start Amps

A

216.0

215.8

226.6

Recommended Mains Fuse Size

A

125

125

125

Max Mains Incoming Cable Size

mm²

70

70

70

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only – W2W2

Nominal Run Amps

A

86.5

97.3

101.9

Maximum Start Amps

A

199.6

210.4

245.7

Recommended Mains Fuse Size

A

100

125

125

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Compressor 1 , Circuit 1 & 2

(3)

Motor Size

kW

7.19

9.46

9.46

Nominal Run Amps

A

12.9

16.9

16.9

Locked Rotor Amps

A

92

130

130

Type of Start

Direct On Line

Compressor 2, Circuit 1 & 2

(3)

Motor Size

kW

9.5

9.5

10.9

Nominal Run Amps

A

16.9

16.9

19.2

Locked Rotor Amps

A

130

130

163

Type of Start

Direct On Line

Standard Dry Cooler Match - AC Motor Per Fan

Quantity x Motor Size

kW

3 x 0.6

4 x 0.88

4 x 0.88

Full Load Amps

A

2.62

1.65

1.65

OPTIONAL EXTRAS

Electric Heating

Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.47

45.47

45.47

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

Standard Size Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Larger Size Motor - EC Motor - Per Fan

Quantity x Motor Size

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Dry Cooler Match - EC Motor-Per Fan

Quantity x Motor Size

kW

3 x 0.73

4 x 1.68

4 x 1.68

Full Load Amps

A

3.3

2.6

2.6

SCAF Dry Cooler Match – Motor – Per Fan

Quantity x Motor Size

kW

3 x 1.4

4 x 1.94

4 x 1.94

Full Load Amps

A

6

3.4

3.4

(1) Values given for full function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor