Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

21

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Liquid Sub Cooling

The degree of liquid sub cooling required to prevent flashing of liquid refrigerant can be calculated by
the following method.

Given the following as an example:

·

Refrigerant R410A

·

Condensing temperature (54.4°C)

·

Liquid lift 20m

·

Piping friction loss 0.21 bar

·

Losses through valves and fittings 0.5 Bar

1.

Determine the pressure drop due to pipe friction = 0.21 Bar

2.

Pressure drop due to valves and fittings = 0.5 Bar

3.

Pressure loss due to liquid lift = height x 0.115 = 20 x 0.115 = 2.3 bar

Note:- At normal liquid temperatures the static pressure loss due to elevation at the top of a liquid lift
0.115 bar/m


Therefore:- Total pressure loss in liquid line = 3.01bar

Condensing pressure @ Condensing temperature (54.4°C) = 34 Bar
Total pressure loss in liquid line = 3.01 Bar
Nett pressure at Expansion valve = 34 - 3.01 = 30.99 bar

Saturation temperature at the Nett pressure at expansion valve (30.99 bar) = 52°C
(from Refrigerant tables)

Sub cooling required

= Condensing temperature — Saturation temperature at the Nett pressure at expansion valve
= 54.4 - 52 = 2.4 °C

Therefore liquid sub cooling required to prevent liquid flashing = 2.4 °C

Packaged Unit Pre-Charged Refrigerant Volumes

Indoor unit

kg / circuit

HGRH kg / circuit

Indoor unit

kg / circuit

HGRH kg / circuit

SC19D055-W2W2

5.75

5.90

SC19D033-W2F0

5.68

5.83

SC19D070-W2W2

7.32

7.47

SC19D038-W2F0

7.25

7.40

SC19D080-W2W2

7.32

7.47

SC19D045-W2F0

7.25

7.40

SC25D080-W2W2

8.51

8.70

SC19D064-W2F0

9.60

9.81

SC25D090-W2W2

10.85

11.07

SC19D070-W2F0

9.61

9.81

SC25D100-W2W2

10.85

11.07

SC19D076-W2F0

9.61

9.82

SC31D100-W2W2

12.04

12.30

SC25D045-W2F0

8.44

8.63

SC31D120-W2W2

12.04

12.30

SC25D050-W2F0

10.78

11.00

SC31D130-W2W2

12.04

12.31

SC25D055-W2F0

10.78

11.00

SC19D033-W2C0

5.68

5.83

SC25D067-W2F0

10.79

11.04

SC19D038-W2C0

7.25

7.40

SC25D073-W2F0

10.79

11.04

SC19D045-W2C0

7.25

7.40

SC25D080-W2F0

10.80

11.04

SC19D064-W2C0

9.60

9.81

SC31D055-W2F0

11.96

12.23

SC19D070-W2C0

9.61

9.81

SC31D065-W2F0

11.97

12.23

SC19D076-W2C0

9.61

9.82

SC31D075-W2F0

11.97

12.23

SC25D045-W2C0

8.44

8.63

SC31D077-W2F0

11.97

12.26

SC25D050-W2C0

10.78

11.00

SC31D080-W2F0

11.98

12.27

SC25D055-W2C0

10.78

11.00

SC31D083-W2F0

11.98

12.27

SC25D067-W2C0

10.79

11.04

SC25D073-W2C0

10.79

11.04

SC25D080-W2C0

10.80

11.04

SC31D055-W2C0

11.96

12.23

SC31D065-W2C0

11.97

12.23

SC31D075-W2C0

11.97

12.23

SC31D077-W2C0

11.97

12.26

SC31D080-W2C0

11.98

12.27

SC31D083-W2C0

11.98

12.27


(1)Fitted with optional hot gas re-heat